From: Jennifer Cline

Sent: Tue Feb 17 15:19:37 2015

To: Troy Collison

Cc: John Sowards; Mark Lietzke; Keith Stiglbauer; Heather Penni

Subject: RE: nervous level transducer at the WTP

Importance: Normal

Attachments: MolallaWTP_Dailer_2015-02-13.pdf;

 

Hi Troy,

I was not able to find his email unfortunately. However, attached is the signed quote for installing a new dialer at the WTP.

Please make sure to Cc me on all futures quotes.

Thanks,

Jennifer Cline, P.E.

City of Molalla

Public Works Director

O: 503.759.0218

F: 503.829.3676

image "file:///C:

From: Troy Collison [mailto:tbc@industrialsystems-inc.com]

Sent: Tuesday, February 17, 2015 2:59 PM

To: Jennifer Cline; Keith Stiglbauer

Cc: John Sowards; Mark Lietzke

Subject: RE: nervous level transducer at the WTP

Please see attached

This was sent by John in our office last Friday.

Thanks

 

troy

From: Jennifer Cline [mailto:jcline@cityofmolalla.com]

Sent: Tuesday, February 17, 2015 2:55 PM

To: Troy Collison; Keith Stiglbauer

Cc: John Sowards; Mark Lietzke

Subject: RE: nervous level transducer at the WTP

Hi Troy,

I have not seen an invoice to approve from Industrial Systems. Can you please email it my way?

Thank You,

Jennifer Cline, P.E.

City of Molalla

Public Works Director

O: 503.759.0218

F: 503.829.3676

image "file:///C:

From: Troy Collison [mailto:tbc@industrialsystems-inc.com]

Sent: Tuesday, February 17, 2015 2:30 PM

To: Keith Stiglbauer

Cc: John Sowards; Mark Lietzke; Jennifer Cline

Subject: RE: nervous level transducer at the WTP

We submitted the proposal to the City as you requested and have had no reply.

Thanks

 

Troy

From: Keith Stiglbauer [mailto:kstiglbauer@cityofmolalla.com]

Sent: Tuesday, February 17, 2015 2:27 PM

To: Troy Collison

Cc: John Sowards; Mark Lietzke; Jennifer Cline

Subject: Re: nervous level transducer at the WTP

Hey what's going on with the dialer?


 

From: "Troy Collison" <tbc@industrialsystems-inc.com>

To: "Keith Stiglbauer" <kstiglbauer@cityofmolalla.com>

Cc: "jns" <jns@industrialsystems-inc.com>, "Mark Lietzke" <msl@industrialsystems-inc.com>, "Jennifer Cline" <jcline@cityofmolalla.com>

Sent: Friday, February 13, 2015 8:15:59 AM

Subject: RE: nervous level transducer at the WTP

We do not have a replacement auto dialer yet.

We are pursuing two possible solution 1) a direct replacement for what you have and 2) any dialer that is available TODAY that could be installed as a stop gap alarm notification tool.

John will keep you posted.

Thanks

Troy

From: Keith Stiglbauer [mailto:kstiglbauer@cityofmolalla.com]

Sent: Friday, February 13, 2015 7:38 AM

To: Troy Collison

Cc: jns; Mark Lietzke; Jennifer Cline

Subject: Re: nervous level transducer at the WTP

Good morning troy

We had another alarm last night with no alarm. Have turned it off. I assume we with not have a dialer today being Friday. And we have a three day weekend. Please let me know ASAP so I can make arrangements to have the plant covered for the weekend. Keith


 

From: "Troy Collison" <tbc@industrialsystems-inc.com>

To: "Keith Stiglbauer (kstiglbauer@cityofmolalla.com)" <kstiglbauer@cityofmolalla.com>

Cc: "jns" <jns@industrialsystems-inc.com>, "Mark Lietzke" <msl@industrialsystems-inc.com>

Sent: Thursday, February 12, 2015 2:43:48 PM

Subject: FW: nervous level transducer at the WTP

Keith

We are assuming the dialer is broken and trying to locate a replacement.

I suppose the fact it called you when there are no alarms present is a good indicator that it IS broker?

Perhaps you should just unplug it?

Troy

From: Keith Stiglbauer [mailto:kstiglbauer@cityofmolalla.com]

Sent: Thursday, February 12, 2015 10:41 AM

To: Troy Collison

Subject: Re: nervous level transducer at the WTP

Just wanted to let you know dialer called last night no alarms at the plant at 11:50 pm.


 

From: "Troy Collison" <tbc@industrialsystems-inc.com>

To: "Keith Stiglbauer" <kstiglbauer@cityofmolalla.com>

Sent: Tuesday, February 10, 2015 7:59:32 AM

Subject: RE: nervous level transducer at the WTP

Awesome thanks

From: Keith Stiglbauer [mailto:kstiglbauer@cityofmolalla.com]

Sent: Tuesday, February 10, 2015 7:58 AM

To: Troy Collison

Subject: Re: nervous level transducer at the WTP

Raco Verbatim V21256 I do have a manual at the plant also.


 

From: "Troy Collison" <tbc@industrialsystems-inc.com>

To: "Keith Stiglbauer" <kstiglbauer@cityofmolalla.com>

Sent: Tuesday, February 10, 2015 7:50:48 AM

Subject: RE: nervous level transducer at the WTP

Keith

Can you give us the model # of the dialer so we can print the manual for it?

Thanks

From: Keith Stiglbauer [mailto:kstiglbauer@cityofmolalla.com]

Sent: Tuesday, February 10, 2015 7:16 AM

To: Troy Collison

Subject: Re: nervous level transducer at the WTP

Please let me know when to expect your staff Tuesday.


 

From: "Troy Collison" <tbc@industrialsystems-inc.com>

To: "Keith Stiglbauer" <kstiglbauer@cityofmolalla.com>

Sent: Monday, February 9, 2015 1:00:29 PM

Subject: RE: nervous level transducer at the WTP

Oh – yes – about the failed dialer.

That is on the list for tomorrow.

I would be surprised if it just lost its programming but we will look at.

From: Keith Stiglbauer [mailto:kstiglbauer@cityofmolalla.com]

Sent: Monday, February 09, 2015 1:00 PM

To: Troy Collison

Subject: Re: nervous level transducer at the WTP

At the water plant did Mark not call you?


 

From: "Troy Collison" <tbc@industrialsystems-inc.com>

To: "Keith Stiglbauer" <kstiglbauer@cityofmolalla.com>

Sent: Monday, February 9, 2015 12:53:18 PM

Subject: RE: nervous level transducer at the WTP

OK Thanks

I like ultra-conic but would have chosen a Siemens Hydro Ranger 200 and XPS 15 transducer.

They are pretty solid and we install probably 10 or 15 a year.

A drop in sensor in a clearwell is still pretty standard too. There is no need to empty the clearwell, just suspend them from a cable pipe.

Anyway, we will be out there tomorrow afternoon.

You have no alarms where?

From: Keith Stiglbauer [mailto:kstiglbauer@cityofmolalla.com]

Sent: Monday, February 09, 2015 12:44 PM

To: Troy Collison

Subject: Fwd: nervous level transducer at the WTP


 

From: "Keith Stiglbauer" <kstiglbauer@cityofmolalla.com>

To: "Jennifer Cline" <jcline@cityofmolalla.com>

Sent: Monday, February 9, 2015 12:38:17 PM

Subject: Re: nervous level transducer at the WTP

The Banner was installed to ease maintenance next time. Don't need to drain wet well to change or repair. By the way I still do not have any alarms?


 

From: "Jennifer Cline" <jcline@cityofmolalla.com>

To: "Keith Stiglbauer" <kstiglbauer@cityofmolalla.com>

Cc: "Jeff Mccrum" <jmccrum@cityofmolalla.com>

Sent: Friday, February 6, 2015 5:50:26 PM

Subject: Fwd: nervous level transducer at the WTP

Hi Keith,

Can you answer Tony's question for him please?

Thanks,

Jenn

 

Sent from my iPhone

 

Begin forwarded message:

From: Troy Collison <tbc@industrialsystems-inc.com>

To: Jennifer Cline <jcline@cityofmolalla.com>

Cc: "Keith Stiglbauer (kstiglbauer@cityofmolalla.com)" <kstiglbauer@cityofmolalla.com>

Subject: nervous level transducer at the WTP

Hi Jennifer

We were not able to get anyone to the WTP today to attempt to adjust the Banner Level sensor installed two months ago.

We have some signal filters being shipped 2nd day. Those should be here next Tuesday. When they arrive either John or I will go out to the WTP to install one and see what we can do with the settings on this unit to eliminate the unwanted signal fluctuations.

In the meantime, I have marked how I would set the selector switches up on this unit and scanned that document in and attached it. (see red marks on pages 2 and 3). This assume the device is intended to produce a 4-20mA signal.

Can I ask what this unit replaced and why? Was it a Miltronics Level sensor? Why was the banner unit installed?

Thank you,

Troy B. Collison

 

 

5835 NE 122nd Avenue, Suite #110

Portland, Oregon 97230

http://www.industrialsystems-inc.com

Phone: 503.262.0367

Cell: 360.957.5039

Fax: 503.262.0371

CCB # 196597 WA #INDUSSI880K9