From: Jennifer Cline
Sent: Wed Apr 08 17:10:11 2015
To:
Subject: Re: Joint restraint for Pacific Fibre fire line extension
Importance: Normal
Thank you. I will be in the office tomorrow and Friday.
Jenn
Sent from my iPhone
On Apr 8, 2015, at 6:25 AM, Hassan Ibrahim <hai@curran-mcleod.com> wrote:
Hi Jenn,
It does, just need to make sure they use the one with the 6 rods if the pipe being installed is larger than 12” in diameter.
Regards,
--------------------
Hassan Ibrahim, P.E.
CURRAN-McLEOD, INC.
6655 SW Hampton St, Ste. 210
Portland, OR 97223
Tel: 503-684-3478
Fax: 503-624-8247
Cell: 503-807-2737
email: hai@curran-mcleod.com
From: Jennifer Cline [mailto:jcline@cityofmolalla.com]
Sent: Tuesday, April 07, 2015 4:51 PM
To: Hassan Ibrahim
Subject: Fwd: Joint restraint for Pacific Fibre fire line extension
Hi Hassan,
I'm unfamiliar with this restraint. Does this meet the same specifications as for the Stowers job?
Thanks,
Jenn
Sent from my iPhone
Begin forwarded message:
From: Mark Erickson - Rotschy Inc <mark.erickson@rotschyinc.com>
To: jcline@cityofmolalla.com <jcline@cityofmolalla.com>
Cc: James Bobst <jbobst@pacfibre.com>, JJolma@gibbs-olson.com <JJolma@gibbs-olson.com>
Subject: Joint restraint for Pacific Fibre fire line extension
Hello Jennifer,
Rotschy Inc. is bidding on the fire line extension for the Pacific Fibre Molalla facility. One of our suppliers has proposed the attached Ford UFR1350-C-16-I bell restraint for the 16” PVC fire line. Is this restraint acceptable to the city of Molalla?
Mark Erickson
Rotschy, Inc.
9210 NE 62nd Ave
Vancouver, WA 98665
O (360) 334-3100
F (360) 334-3101
C (360) 624-3751