From: Rusty Pressnall
Sent: Wed Jul 15 09:33:01 2015
To: 'Jennifer Cline'
Subject: RE: Molalla Force Main Repair
Importance: Normal
Hi Jennifer,
When your guys get the pipe between the 90 and the reducer exposed, we need to get an OD tape on both pipe sizes. I noticed the drawing says 24” DIPS which is fairly uncommon around here, usually we use IPS pipe.
24” DIPS is 25.80” OD, 24” IPS is 24.00” OD.
8” DIPS is 9.05” OD, 8” IPS is 8.625” OD.
It’s important to verify what the pipe OD’s are and what the pressure rating needs to be so we can have everything built correctly.
Thanks,
Rusty
Rusty Pressnall | Service Manager
HD Fowler Company | Bellevue Branch
Phone: (425) 748-5348
Fax: (425) 641-8885 | Cell: (425) 449-9701
From: Jennifer Cline [mailto:jcline@cityofmolalla.com]
Sent: Tuesday, July 14, 2015 10:28 AM
To: Rusty Pressnall
Subject: Molalla Force Main Repair