From: Bill Avison

Sent: Thu Mar 30 10:28:02 2017

To: Mike Penunuri

Cc: Gerald Fisher; Vince Stafford

Subject: Re: Hydrants

Importance: Normal

 

Mike,

 

Thanks for the update. I have scheduled a meeting with the gentleman that is going to clear the blackberries next Wednesday the 5th. I also have a call in to the FireStop folks to schedule an inspection of the sprinkler system. I'll give you a progress update next week.

 

Thanks,

 

BILL AVISON

President

AVISON LUMBER CO.

PO Box 419 | Molalla, OR 97038

503-849-2877 | bill@avison.com

503-829-9001 Office | 503-210-1200 Fax

 

 

On Mar 29, 2017, at 1:49 PM, Mike Penunuri <penunuri@molallafire.org> wrote:

 

Good afternoon Bill. I finally had the opportunity to check they hydrants at your site off of West Main. The fire hydrant just past the gate, is functional. However, when opened, water is coming from the top nut on the hydrant. This hydrant will need maintenance. I was unable to get flow readings for the water supply at this site due to not being able to access the hydrant at the rear of the property as it, as well as the FDC for the sprinkler system, is overgrown in berry briers. I have attached photos. These need to be cut back so that the hydrant and FDC are accessible. As far as the sprinkler system goes, the last test/inspection date as per the tag on the riser, was 2015. NFPA 25 Chapter 5 section 5.1.1.2 requires at least annual inspection and maintenance. The sprinkler system is required for vehicle maintenance building at the rear of the property and will need to be serviced. When we spoke several weeks back, you mentioned something about possibly new construction at this site. With the current configuration of the buildings, the hydrant spacing is minimally effective. If new buildings or construction is to be done at this site, additional hydrants and repair of the line will be required. Please let me know when they hydrant and FDC have been cleared, and I will test the system and get you accurate flow rates.

Michael C. Penunuri

Lieutenant/Paramedic

ICC Inspector II

N.F.P.A. Inspector III

503-829-2200 Ext 104

Fax 503-829-5794

This message is confidential. It may also be privileged or otherwise protected by work product immunity or other legal rules. If you have received it by mistake, please let us know by e-mail reply and delete it from your system; you may not copy this message or disclose its contents to anyone.

<IMG_0437.JPG><IMG_0436.JPG>