Good morning Nicholas. I spoke with Brentwood representatives several months back about this project they are facing two issues that need to be resolved.

1) Combining /attaching two building of that size pushes them in to a required sprinkler system as per Oregon Fire Code section 903.2.9

2) They are storing dried hardwood materials on racks above 12 feet in height. As per the definitions in chapter 2 on page 29, this is now high pile combustible storage. Due to the high pile storage, it pushes them in to a sprinkler system.

When I met with them previously I had informed them that in the first pole building, the sprinkler system was missed by Molalla Fire and Clackamas County and due to catching the issue on a final, the agreement was no storage was to be above 12 feet. I checked several times and the storage was always above this height. I don’t believe they were doing this maliciously but with how their product is shipped to them in combination with how it is stored on racks, this is impractical and impossible to maintain storage below 12 feet in height. They need to fully submit to Clackamas County construction documentation as required in the Oregon Fire Code in section 3201.3 so a true evaluation of the building can be made. They can view the code sites at the below link and click on the adopted codes tab and scroll down to 2014 Oregon Fire Code.

http://oregonbcd.org/programs/online_codes.html

Michael C. Penunuri

Lieutenant/Paramedic

ICC Inspector II

N.F.P.A. Inspector III

503-829-2200 Ext 104

Fax 503-829-5794

This message is confidential. It may also be privileged or otherwise protected by work product immunity or other legal rules. If you have received it by mistake, please let us know by e-mail reply and delete it from your system; you may not copy this message or disclose its contents to anyone.

From: Nicolas Lennartz [mailto:nlennartz@cityofmolalla.com]

Sent: Wednesday, June 29, 2016 11:51 AM

To: 'Mike Penunuri' <penunuri@molallafire.org>; gfisher@cityofmolalla.com

Subject: File P41-2016

Mike and Gerald,

 

I am reviewing an expansion of lumber storage for Brentwood Industries at 453 Industrial Way. They propose to add 7800 square feet to an existing 4800 sq. ft. pole building. If you could forward any comments prior to July 13, I will be issuing a decision on or after that date.

 

Nothing leads me to believe they propose to add sewer or water to the structure. Mike, he says he has talked with you about meeting fire codes, so I hope this isn’t a surprise.

 

Thanks, let me know of any questions.